Tuesday, August 9, 2011

Typical Switched Wiring Circuits For A Lighting Installation

Whichever type of fitting you intend to use, draw a scale floor plan of the room, clearly mark where items are and where you wish relevant lights to be. When you have completed your plan, mark the ceiling / wall with the centre position of the fitting, making sure you mark the position of cutouts, before cutting or drilling, ensuring there are no obstructions, cable or pipes behind. Fitting lights on the ground floor may require you to have access to the floor above so ensure floorboards can be accessed.

If installing recessed down lights ensure there is enough clearance in the ceiling void, you will find minimum distances stated in the supplied instructions. Ensure the integrity of any fire barrier is maintained especially where there is a dwelling above the site of the fitting(s).



FIG. 6 show typical switched wiring circuits for a lighting installation.


alternatively you can use the existing 230V supply from the loop-in terminals of a ceiling rose supplying existing 230V lighting. Always read the light fittings instructions before attempting any work and if in doubt, consult a qualified electrician. Lighting circuits are usually controlled from a 5amp fuse at the main board and most new installations require this to be protected by an RCD operating at 30mA. In a two-storey house there are usually two lighting circuits, one for each floor.

Using the above information, you should now be able to calculate the amount of cable and where any switches should go. NOTE: always allow extra cable as it is easier to trim back than to add. This will also give you some flexibility if you have to adjust the positioning of a fitting.

Fitting Lights And Electrical Connections


Installing a light fitting is straightforward but at this stage don't fit lamps into their housings. Once all the cabling is in place you can then fix any brackets using suitable fixings ( taking care not to drill or screw through any cables ). Ensure all terminations are secure and comply with the Wiring Regulations that your light fitting complies with BS EN 60598, the British Standard for light fittings.

NOTE: Fittings classed as Double Insulated ( Class II ) or SELV ( Class III ) do not require an earth and fitting instructions should be followed. TIP: When using multiple lamp fittings, or when low voltage fittings are supplied via a transformer, a bulb / lamp reaches the end of its life; it is good practice, to replace as soon as possible. Failure to do so may cause 'overvolting' of the other bulbs / lamps and could reduce their lifespan by up to 50%. Always ensure that the bulbs / lamps are sufficiently cool before replacing.

Detection Of Motion


with the European Standard for luminaries (BS EN 60598) and carry a CE mark. Depending on where the light fitting is to be sited will determine the degree of protection the product will need against ingress of moisture. This is known as an IP rating i.e. IP44. Simply put, the first number of an IP rating (0-6) is the degree of protection against debris, dust and even 'little fingers' getting in. The second number (0-8) is its resistance to moisture. IP68 is the highest degree of protection offered against dust, solid objects & moisture.

Outdoor Light Of Materials And Dccessories Required


Outdoor light fittings will require some maintenance, so choose one made from a material suitable for the local environmental conditions i.e. if you live near to the sea, select a plastic or marine grade stainless steel product that will require minimal cleaning and is not prone to corrosion. Always check manufacturer's zcare instructions.

Having decided, what, where, how you wish to light and how many different moods you want to create, make a plan of your garden, identifying lengths, quantities of materials and accessories required. These may include switches, P.I.R. sensors, conduit, armoured cable (above 50V), an RCD, fixings, weatherproof junctions boxes, cable joints, glands etc.

NOTE: Outdoor Fittings operating under 50V can use conduit to protect the cable. Fittings operating above 50V must use armoured cable and be protected by a RCD, with a residual operating current not exceeding 30mA.

Once you have selected your fittings and accessories, using your plan, physically mark out the areas in your garden where the lighting is to be sited and the cable is to be run. Prepare the ground for the cables by digging channels - for cables operating at above 50V or where the ground is likely to be disturbed, the trench must be at least 500mm deep.

The cable route should be marked with yellow and black tape. It should be just 150mm below the surface, above buried cable; this is to warn persons excavating the ground in the future that a cable is present. It is also a good idea to keep a garden plan showing all cable routes and depths for future reference.

NOTE: When laying cable, always leave an extra length for any last minute adjustments; it is easier to reduce the length than it is to add. Don't back fill until you have completed, tested and are happy with the positioning of the system.

When installing recessed ground lighting in a drive or pathway, you should provide suitable drainage; bedding the base of the fitting onto gravel can easily do this.

Once all the cabling is in place and you are happy with the location of the fittings, make sure the securing method is suitable for the size and weight of the fitting, the surface to which it is to be fixed and its exposure to the elements. When all this is done, connect the supply cable, re-check all connections and fit bulbs / lights. Only when you are happy with the installation and it has been checked, can an 'Authorised Competent Person' connect the mains power supply. Switch on and test. Back fill any trenches and make good.

Even the best garden lighting designers don't always get it right first time. If this happens to you, it may just be a case of a little adjustment or even some trial and error but it's worth persevering. You can easily add a new circuit or more lights if necessary.

NOTE: Always keep your garden lighting plans for future reference.

All outdoor electrical work must conform to BS 7671 the current IEE wiring regulations, and Part P of Building Regulations, you are advised to check with your local authorities Building Control Department, or an Authorised Competent Person, before starting. If in any doubt about electrical work, contact a qualified person.

Source: http://www.ledaladdin.com/Install_LED_Light_Wiring_Diagram/typical_switched_wiring_circuits_for_a_lighting_installation.html

Window Covering Design

The selection of blinds, window coverings, or the lack thereof is likely the most crucial choice a designer will make when seeking to ensure visual comfort while maintaining daylight performance over time. We have all seen buildings where blinds are down continuously. Typically, this is associated with visual discomfort (glare). The most common source of glare issues in daylighting is a line of sight to the disk of the sun. Selecting a window covering that is opaque enough to block the sun, such as fabric window shades with 3% or less openness or horizontal blinds, can control this phenomena.

Manually operated blind systems can be very effective if properly used. More specifically, a 2" horizontal blind with a white finish can function as a series of mini light shelves casting indirect light into the space when desired. However, they rely on and require constant user attention to maintain complete glare control while achieving maximum daylight performance. For this reason, blinds or shades are often permanently deployed at the ¡°worst case scenario¡± position to maintain visual comfort throughout the day and year. This typically results in poor daylight performance and the elimination of views to the exterior.

Automated glare control has the distinct advantage of being deployed only when needed and retracting without user intervention when direct sunlight is no longer present to allow for unimpeded diffuse daylight. In most cases, this will deliver longer periods of effective daylight contribution, increased electric lighting power savings, and longer durations of unobstructed views to the exterior. Automation of glare control may provide the most persistent daylight performance where low angle direct sun is present during extended periods of occupancy.

< Direct sunlight can cause visual discomfort. Shutting the blinds here would eliminate the benefit of the daylight.




Example of split window covering strategy to preserve views or block sun where needed, allowing for indirect light into space. >

Shading and Exposure Tips:


  • North - Shading may only be needed in early morning or late afternoon.
  • South - Good access to strong illumination but varies throughout the year. Shading is easier than East/West.
  • East/West - Shading is difficult but critical for comfort.
Source: http://www.ledaladdin.com/Install_LED_Light_Wiring_Diagram/Window_Covering_Design.html

LED Light Guide Formulas

Demand for Power (kW) =System Input Wattage (W) ÷ 1,000
Energy Consumption (kWh) = System Input Wattage (kW) x Hours of Operation/Year
Hours of Operation/Year = Operating Hours/Day x Operating Days/Week x Operating Weeks/Year
Lighting System Efficacy (Lumens per Watt or LPW) = System Lumen Output ÷ Input Wattage
Unit Power Density (W/sq.ft.) = Total System Input Wattage (W) ÷ Total Area (Square Feet)
Watts (W) = Volts (V) x Current in Amperes (A) x Power Factor (PF)
Voltage (V) = Current in Amperes (A) x Impedance (Ohms) [Ohm's Law]

ECONOMIC FORMULAS
Simple Payback on an Investment (Years) = Net Installation Cost ($) ÷ Annual Energy Savings ($)
5-Year Cash Flow ($) = 5 Years - Payback (Years) x Annual Energy Savings ($)
Simple Return on Investment (%) = [Annual Energy Savings ($) ÷ Net Installation Cost ($)] x 100

DESIGN FORMULAS
Footcandles & Lumens
Footcandles (fc) = Total Lumens (lm) ÷ Area in Square Feet
1 Lux (lx) = 1 Footcandle (fc) x 10.76
Lux = Total Lumens ÷ Area in Square Meters

Calculating Light Level at a Point
For planes perpendicular to the direction of candlepower (Inverse Square Law):
Footcandles (fc) = I ÷ D2
I = Candlepower in candelas (cd) D = Direct distance between the lamp and the point where light level is calculated

Many workplanes are not perpendicular to the direction of light intensity, which is why calculating light level at a point is useful for such applications. In these cases, we often must determine light levels on workplanes that are not horizontal and perpendicular but tilted or even vertical. For tilted-horizontal or vertical planes:
Horizontal Footcandles (fch) = (I ÷ D2) x H
Vertical Footcandles (fcv) = (I ÷ D2) x L

I = Candlepower in candelas (cd) D = Direct distance between the lamp and the point where light level is calculated
H = Distance between the lamp and the point direct below on the workplane
L = Distance between that point and the point where light level is being calculated
D = Square Root of (H2 + L2) or D2 = H2 + L2

Calculating Average Light Level Throughout a Space (three formulas)
Average Maintained Illumination (Footcandles) = (Lamps/Fixture x Lumens/Lamp x No. of Fixtures x Coefficient of Utilization x Light Loss Factor) ÷ Area in Square Feet Average Maintained Illumination (Footcandles) = (Total Lamps x Lumens/Lamp x Coefficient of Utilization x Light Loss Factor) ÷ Area in Square Feet
Average Maintained Illumination (Footcandles) = (Lamps in One Fixture x Lumens/Lamp x Coefficient of Utilization x Light Loss Factor) ÷ Area in Square Feet/Fixture
Lumen Method
Required Light Output/Fixture (Lumens) = (Maintained Illumination in Footcandles x Area in Square Feet) ÷ (Number of Fixtures x Coefficient of Utilization x Ballast Factor x Light Loss Factor)

Light Loss Factors (more on Light Loss)
Light Loss Factor (LLF) = Ballast Factor x Fixture Ambient Temperature Factor x Supply Voltage Variation Factor x Lamp Position Factor x Optical Factor x Fixture Surface Depreciation Factor x Lamp Burnouts Factor x Lamp Lumen Depreciation Factor x Fixture Dirt Depreciation Factor x Room Surface Dirt Depreciation Factor
Lamp Burnout Factor = 1 - Percentage of Lamps Allowed to Fail Without Being Replaced

Zonal Cavity Method (determining cavity ratios)
Room Cavity Ratio (for regular rooms shaped like a square or rectangle) = [5 x Room Cavity Depth x (Room Length + Room Width)] ÷ (Room Length x Room Width) Room Cavity Ratio (for irregular-shaped rooms) = (2.5 x Room Cavity Depth x Perimeter) ÷ Area in Square Feet
Ceiling Cavity Ratio = [5 x Ceiling Cavity Depth x (Room Length x Room Width)] ÷ (Room Length x Room Width)
Floor Cavity Ratio = [5 x Floor Cavity Depth x (Room Length x Room Width)] ÷ Room Length x Room Width
Room surface reflectances can be predicted in a new design or measured in an existing facility. If existing facility:
Room Surface Reflectance (%) = Reflected Reading ÷ Incident Reading Reflected Reading = Measurement from a light meter holding it about 1.5 feet away from the surface with the sensor parallel and facing the surface.
Incident Reading = Measurement from a light meter held flat against the surface and facing out into the room.

Calculating Number of Lamps And Fixtures And Spacing
Required No. of Fixtures = (Lumens/Lamp x No. of Lamps x Coefficient of Utilization x Light Loss Factor x Area in Square Feet) ÷ (Lumens/Lamp x Lamps/Fixture x Coefficient of Utilization x Light Loss Factor)
Required Lamps = Required Lumens ÷ Initial Lumens/Lamp
Maximum Allowable Spacing Between Fixtures= Fixture Spacing Criteria x Mounting Height
Fixture Spacing Criteria: See the manufacturer's literature Mounting height: Distance in feet between the bottom of the fixture and the workplane

Spacing Between Fixtures = Square Root of (Area in Square Feet ÷ Required No. of Fixtures)
Number of Fixtures to be Placed in Each Row (Nrow) = Room Length ÷ Spacing
Number of Fixtures to be Placed in Each Column (Ncolumn) = Room Width ÷ Spacing
For the above two formulas, round results to the nearest whole integer.

Spacingrow = Room Length ÷ (Number of Fixtures/Row - 1/3)
Spacingcolumn = Room Width ÷ (Number of Fixtures/Column -1/3)

If the resulting number of fixtures does not equal the originally calculated number, calculate impact on the designed light level:
% Design Light Level = Actual No. of Fixtures ÷ Originally Calculated No. of Fixtures

To calculate fixtures mounted in continuous rows:
Number of Luminaires in a Continuous Row = (Room Length ÷ Fixture Length) - 1
Number of Continuous Rows = Total Number of Fixtures ÷ Fixtures Per Row

MAINTENANCE
Lamp Life
Calendar Lamp Life (Years) = Rated Lamp Life (Hours) ÷ Annual Hours of Operation (Hours/Year)

Lamp Burnout Factor
Lamp Burnout Factor = 1 - Percentage of Lamps Allowed to Fail Without Being Replaced

Group Relamping Cost
Annualized Cost ($) = A x (B + C)
A = Operating Hours/Year ÷ Operating Hours Between Relampings
B = (Percentage of Lamps Failing Before Group Relamping x Number of Lamps) x (Lamp Cost + Labor Cost to Spot Replace 1 Lamp)
C = (Lamp Cost, Group Relamping + Labor Cost to Group Relamp 1 Lamp) x Number of Lamps

Spot Relamping Cost
Average Annual Cost ($) = (Operating Hours/Year ÷ Rated Lamp Life) x (Lamp Cost + Labor Cost to Replace 1 Lamp) x Total Number of Lamps

Cleaning Cost
Cleaning Cost ($) = Time to Wash 1 Fixture (Hours) x Hourly Labor Rate ($) x Number of Fixtures in Lighted Space

ENVIRONMENTAL IMPACT
Average Reduced Air Pollution (lbs. Carbon Dioxide) = Energy Savings (kWh) x 1.6 lbs.
Average Reduced Air Pollution (g. Sulphur Dioxide) = Energy Savings (kWh) x 5.3 g.
Average Reduced Air Pollution (g. Nitrogen Oxides) = Energy Savings (kWh) x 2.8 g.
Pounds = Grams ÷ 454
Tons = Pounds ÷ 2,000

Source: http://www.ledaladdin.com/light_guides/led_light_guide_formulas.html

The Chip-on-Board (COB) LED Module

The Chip-on-Board (COB) LED Module

LED technology offers better color mixing and simplified thermal management for backlighting large LCD displays.

Conventionally, LED chips have been mounted on substrates to create discrete LED components, which were attached to a printed circuit board. The solder reflow process typically used to attach the component to the circuit board subjects the LED chip to a substantial amount of heat that easily can damage the chip or degrade its performance. Hence, tight (and, therefore, expensive) process control is required for this type of assembly. In fact, the substrate cost is almost invariably the second-highest in an LED component, exceeded only by the cost of the chip itself.

A different approach, called chip-on-board packaging, seems capable of meeting all the requirements of backlighting. This method mounts the LED chip directly onto the printed circuit board using a conductive adhesive, which helps reduce costs by eliminating the substrate and complicated solder reflow assembly process. In addition, direct attachment can reduce the pitch between LED chips from the conventional 5 mm to approximately 2 mm and can lower the overall height of the light source (Figure 1).
chip-on-board-approach
Figure 1. By mounting the LED directly onto the printed circuit board, a substrate is unnecessary, so pitch is reduced from 5 mm to approximately 2 mm.

Decreasing the LED pitch reduces the color-mixing area required (Figure 2), which means that the area of light loss is smaller. To achieve high coupling efficiency from the light source to the lightguide plate, a reflector is incorporated into the chip-on-board package to produce an oval radiation pattern. A narrow radiation pattern on the X-axis allows more light to enter the lightguide plate, whereas a wider radiation angle on the Y-axis enhances color mixing.

cob-led-light-color-mixing

Figure 2. Reducing the pitch decreases the size of the color-mixing area.


Simple thermal management

A metal core printed circuit board is used in the package to provide a low thermal resistance, allowing heat generated by the LED chip to be transferred to the heat sink via the shortest possible thermal path (Figure 3), which increases the life span; moveover, the heat transfers more efficiently through three layers than through five. The chip-on-board packages are mounted directly onto the back metal (with thermal compound at the interface), so that the heat generated by the LED chips spreads efficiently on the large metal frame for efficient dissipation without additional heat sinking. In the demonstration configuration, the entire backlight unit can maintain a temperature below 60°.

cob_led_light_Simple_thermal_management

Figure 3. In comparison with the conventional approach, the thermal path is reduced. (DA = die attach, MCPCB = metal core printed circuit board.)

When compared with assemblies using conventional discrete LED packages, a chip-on-board approach can be compared with RGB LED-based LCD backlighting. The chip-on-board leds packaging has a thin outline, it produces better color mixing, and it requires simple thermal management and potentially lowers costs, all of which better match the requirements of customers. In addition, assembling a complete backlight using the chip-on-board led package is similar to that using today fluorescent lamps, which makes a changeover relatively simple.

Source: http://www.ledaladdin.com/led_technology/chip_on_board_leds.html

Friday, August 5, 2011

LED осветление тръба Led крушки замяна доведе захранване Led светлини

LED осветление производители
LED осветление фабрика
LED крушки осветление
LED осветление доставчик
LED светлина тръби
LED лампи производители
LED светлини тръба
LED осветление производителя в Китай
LED светлини крушка
LED лампи фабрика


Китай LED осветление фабрика
LED лампи доставчик
Китай LED лампи производители
LED лампи, крушка
Китай LED осветление доставчик
LED лампи фабрика в Китай
LED лампи, тръби
Енергийна ефективност LED осветителни решения
LED крушки тръба
LED лампи доставчик в Китай
Led assenmbly
LED лампи осветление
енергоспестяващи електрически крушки
Върховен Power LED осветителни тела
закрит доведе осветителни тела
LED крушки
Начална доведе осветителни тела
LED крушки лампа
доведе светлинен ефикасността
Супер ярки светодиодно осветление
LED осветление тръба
Led крушки замяна
доведе захранване
Led светлини
довело Китай
LED крушка осветление

LED peru lýsing leiddi Kína Led ljós leiddi aflgjafa LED rör lýsing LED lampar lýsing

LED framleiðendur lýsing
LED lýsing verksmiðju
LED perur lýsing
LED lýsing birgir
LED ljós slöngur
LED lampar framleiðendur
LED ljós túpa
LED lýsing framleiðanda í Kína
LED ljós peru
LED lampar verksmiðju
Kína LED lýsing verksmiðju


LED lampar birgir
Kína LED lampar framleiðendur
LED lampar peru
Kína LED lýsing birgir
LED lampar verksmiðju í Kína
LED lampar túpa
Orka duglegur LED lausnir lýsing
LED perur túpa
LED lampar birgir í Kína
Led assenmbly
LED lampar lýsing
orkusparandi ljósaperur
hár máttur leiddi lightings
innanhúss leiddi lightings
LED ljósaperur
Forsíða leiddi lightings
LED perur lampi
leiddi lýsandi verkun
Super björt leiddi lýsing
LED rör lýsing
Led skipti perur
leiddi aflgjafa
Led ljós
leiddi Kína
LED peru lýsing

Wednesday, August 3, 2011

Lampy LED dostawca w Chinach Led assenmbly LED świetlówki żarówkami energooszczędnymi oświetlenie LED wysokiej mocy

Producenci oświetlenia LED
Fabryka oświetlenia LED
Żarówki LED oświetlenie
Dostawca oświetlenia LED
Lampy LED
Lampy LED producentów
LED tube
LED producentem oświetlenia w Chinach
Żarówka LED
Fabryka lamp LED
porcelana oświetlenie LED fabryki
Lampy LED dostawca
Chiny producentów lamp LED
Lampy LED żarówki
porcelana oświetlenie LED dostawca
Lampy LED fabryki w Chinach
Lampy LED tube
Energooszczędne rozwiązania oświetleniowe LED
Żarówki LED tube
Lampy LED dostawca w Chinach
Led assenmbly
LED świetlówki
żarówkami energooszczędnymi
oświetlenie LED wysokiej mocy
oświetlenie LED wewnątrz
Żarówki LED
oświetlenie LED do domu
Żarówki LED lampy
doprowadziły skuteczność świetlną
Super jasne diody LED oświetlenie
Oświetlenie LED tube
Wymiana żarówki LED
Zasilacz LED
Led światła
spowodował, że Chiny
Żarówka LED

لامپهای چراغ صرفه جویی در انرژی لامپ قدرت بالا به رهبری چراغ های برق در محیط داخلی به رهبری چراغ های برق به رهبری نور لامپ


تولید چراغ روشنایی
چراغ روشنایی کارخانه
لامپ های روشنایی چراغ
چراغ روشنایی منبع
به رهبری نور لوله
تولید کنندگان لامپ چراغ
چراغ لوله چراغ
تولید کننده وسایل روشنایی چراغ در چین
چراغ لامپ چراغ
چراغ کارخانه لامپ
چین کارخانه چراغ روشنایی
تامین کننده لامپ چراغ
چین تولید کنندگان لامپ چراغ
لامپ لامپ چراغ
چین به رهبری منبع روشنایی
LED lamps factory in china
لامپ های لوله چراغ
راه حل های کارآمد انرژی نور چراغ
لامپ های لوله چراغ
تامین کننده لامپ چراغ در چین
لامپهای چراغ
صرفه جویی در انرژی لامپ
قدرت بالا به رهبری چراغ های برق
در محیط داخلی به رهبری چراغ های برق
به رهبری نور لامپ
خانه رهبری چراغ های برق
لامپ لامپ چراغ
رهبری اثر نورانی
سوپر رهبری درخشان روشنایی
چراغ روشنایی لوله
رهبری لامپ جایگزین
رهبری منبع تغذیه
چراغ هدایت
رهبری چین
نور لامپ چراغ

LED-belysning rør sparepærer høj effekt førte lightings

LED-belysning producenter
LED-belysning fabrik
LED-belysning pærer
LED-belysning leverandør
LED-lys rør
LED lamper producenter
LED-røret lyser
LED belysning producent i Kina
LED pære lyser
LED lamper fabrik
Kina LED belysning fabrikken
LED lamper leverandør
Kina LED lamper producenter
LED pære lamper
Kina LED belysning leverandør
LED lamper fabrik i Kina
LED rør lamper
Energieffektive LED-belysning-løsninger
LED rør pærer
LED lamper leverandør i Kina
Led assenmbly
LED-belysning rør
sparepærer
høj effekt førte lightings
Indendørs LED lightings
LED pærer
hjem førte lightings
LED pærer
førte lysudbytte
Super Bright LED belysning
LED-røret belysning
Led udskiftning pærer
førte strømforsyning
Led lys
førte Kina
LED pære belysning

Indoor-LED-Beleuchtungen LED-Lampen Indoor-LED-Beleuchtungen

LED-Beleuchtung Hersteller
LED-Beleuchtung Fabrik
LED-Beleuchtung Lampen
LED-Beleuchtung Lieferanten
LED Lichtschläuche
LED-Lampen Hersteller
LED Röhre leuchtet
LED-Beleuchtung Hersteller in China
LED-Lampe leuchtet
LED-Lampen Fabrik
China LED-Beleuchtung Fabrik
LED-Lampen Lieferant
China LED-Lampen Hersteller
LED Leuchtmittel Lampen
China LED-Beleuchtung Lieferanten
LED-Lampen-Fabrik in China
LED-Schlauch-Lampen
Energieeffiziente LED-Lichtlösungen
LED-Schlauch Glühbirnen
LED-Lampen Lieferant in China
Led assenmbly
LED Leuchtröhren
Energiesparlampen
High Power LED Beleuchtungen
Indoor-LED-Beleuchtungen
LED-Lampen
Zuhause LED-Beleuchtungen
LED Glühbirnen
führte Lichtausbeute
Super helle LED-Beleuchtung
LED-Schlauch Beleuchtung
Led Ersatzlampen
LED-Netzgerät
Led Leuchten
China führte
LED-Lampe Beleuchtung

Китай светодиодное освещение поставщиком Светодиодные лампы завод в Китае

Светодиодные производителей светотехники
Светодиодное освещение завода
Светодиодные лампы освещения
Светодиодное освещение поставщиком
Свет труб
Светодиодные лампы производителей
Светодиодные фары трубки
Светодиодные производителя освещения в Китае
Светодиодные фары лампа
Светодиодные лампы завод
Китай светодиодного освещения завода
Светодиодные лампы поставщиком
Китай Светодиодные лампы производителей
Светодиодные лампы лампа
Китай светодиодное освещение поставщиком
Светодиодные лампы завод в Китае
Светодиодные лампы трубки
Энергосберегающие светодиодные световые решения
Светодиодные лампы трубки
Светодиодные лампы поставщиков в Китае
Led assenmbly
Светодиодных трубок освещения
энергосберегающие лампочки
СИД наивысшей мощности светильников
Крытый Светодиодные светильники
Светодиодные лампочки
Главная Светодиодные светильники
Светодиодные лампы лампы
привело светоотдача
Супер яркое светодиодное освещение
Светодиодное освещение трубки
Led луковицы замены
привело питания
Водить
LED CHINA
Светодиодное освещение лампы

Led assenmbly Светодиодных трубок освещения энергосберегающие лампочки

Светодиодные производителей светотехники
Светодиодное освещение завода
Светодиодные лампы освещения
Светодиодное освещение поставщиком
Свет труб
Светодиодные лампы производителей
Светодиодные фары трубки
Светодиодные производителя освещения в Китае
Светодиодные фары лампа
Светодиодные лампы завод
Китай светодиодного освещения завода
Светодиодные лампы поставщиком
Китай Светодиодные лампы производителей
Светодиодные лампы лампа
Китай светодиодное освещение поставщиком
Светодиодные лампы завод в Китае
Светодиодные лампы трубки
Энергосберегающие светодиодные световые решения
Светодиодные лампы трубки
Светодиодные лампы поставщиков в Китае
Led assenmbly
Светодиодных трубок освещения
энергосберегающие лампочки
СИД наивысшей мощности светильников
Крытый Светодиодные светильники
Светодиодные лампочки
Главная Светодиодные светильники
Светодиодные лампы лампы
привело светоотдача
Супер яркое светодиодное освещение
Светодиодное освещение трубки
Led луковицы замены
привело питания
Водить
LED CHINA
Светодиодное освещение лампы

Monday, August 1, 2011

LED Spotlight Manufacturers (Chip On Board) COB LEDs Technology

  • (Chip On Board) COB Technology provides the greatest benefits for producing homogeneous light effects and high luminous densities.
  • No UV or IR in the spectrum.
  • No Dazzling and mild color with light bending effect.
  • Energy-saving, Environment friendly, and only 20% power consumption of halogen lamp and incandescent lamp.
  • Aluminum-alloy lamp housing for superior heat dissipation.
  • Particularly designed constant current driver for open or short circuit protection.
spot lights

LED Spotlight using a surface light emitting Chip On Board (COB) LEDs .

COB LED Spotlight MR16 3W

  • Nominal Wattage : 3 W
  • Radiator Temp: < 50 °C
  • Dimensions: L: 62 mm × Φ: 50 mm
  • Luminous Flux : 180LM / 210LM / 240LM
  • Color Temperature : 3000K / 4000K / 6400K
  • LED Spotlight Using A Surface Light Emitting ( Chip On Board ) COB LEDs
par 38 light

COB LED Spotlight GU10 3W

  • Nominal Wattage : 3 W
  • Radiator Temp: < 50 °C
  • Dimensions: L: 70 mm × Φ: 50 mm
  • Luminous Flux : 180LM / 210LM / 240LM
  • Color Temperature : 3000K / 4000K / 6400K
  • LED Spotlight Using A Surface Light Emitting ( Chip On Board ) COB LEDs
par 38 light

COB LED Spotlight E14 3W

  • Nominal Wattage : 3 W
  • Radiator Temp: < 50 °C
  • Dimensions: L: 86 mm × Φ: 50 mm
  • Luminous Flux : 180LM / 210LM / 240LM
  • Color Temperature : 3000K / 4000K / 6400K
  • LED Spotlight Using A Surface Light Emitting ( Chip On Board ) COB LEDs

Lighting Metrics: Quantity, Quality, Efficiency

Because some 85% of human impressions are visual, proper quantity and quality of light are essential to optimum performance. The mission of lighting management is to provide the optimum quantity and quality of light to its users at the lowest operating cost.

Lighting metrics are used to understand and predict how a lighting system will operate. They deal with quantity of light (light output and light levels), quality of light (brightness and color), and fixture efficiency (electrical efficiency and how much light leaves the fixture).

QUANTITY OF LIGHT

Luminous Flux (Light Output). This is the quantity of light that leaves the lamp, measured in lumens (lm). Lamps are rated in both initial and mean lumens.

Initial lumens indicate how much light is produced once the lamp has stabilized; for fluorescent and high-intensity discharge (HID) lamps, this is typically 100 hours.

Mean lumens indicate the average light output over the lamp's rated life, which reflects the gradual deterioration of performance due to the rigors of continued operation; for fluorescent lamps, this is usually determined at 40% of rated life.

A number of factors affect a lamp's light output over time, including lamp lumen depreciation, the lamp's interaction with the ballast, supply voltage variations, dirt or dust on the lamp, and the ambient temperature in the fixture.

To avoid confusion, note that "lumen output" is a term also used to describe a fixture's light output, not just a lamp's. Even more factors can affect light output in this case, including the distribution characteristics of the fixture, fixture surface depreciation, and dirt and dust buildup.

Illuminance (Light Level). This is the amount of light measured on the workplane in the lighted space. The workplane an imaginary horizontal, tilted or vertical line where the most important tasks in the space are performed. Measured in footcandles (fc) (or lux in metric), light levels are either calculated or, in existing spaces, measured with a light meter. A footcandle is actually one lumen of light density per square foot; one lux is one lumen per square meter. Like lumens, footcandles can be produced as either initial or maintained quantities.

Initial footcandles indicates a light level after new lamps are installed.

Maintained footcandles indicates a light level after light loss factors are considered over a period of time. Light loss factors include those affecting light output (see above) and also room surface reflectances, room size/proportions, dirt and dust buildup. While light output may describe either the output of a light source or fixture, maintained footcandles always takes into account the efficiency of the fixture in transmitting light to the workplane.

The human eye is a sophisticated piece of machinery; it is able to adjust to a wide range of light levels, including about 10,000 footcandles on a sunny day to about 0.01 footcandles under full moonlight. However, optimum ranges of light levels have been established for various tasks so that those tasks are performed most efficiently (reading a magazine, for example, would be difficult under moonlight, while 10,000 footcandles would be excessive).

For more information, see Lighting Design Basics and Light Loss Factors.

QUALITY OF LIGHT

Luminance (Photometric Brightness). The light that we actually see, brightness can be measured as the light leaving a lamp, or the light reflecting from an object's surface. If not controlled, brightness can produce levels of glare that either impair or prevent a desired task being performed. Glare can be described as direct or reflected glare, which can then result in discomfort or disability.

Direct glare comes straight from the light source.

Reflected glare shows up on the task itself, such as a computer screen.

Discomfort glare does not prevent seeing makes it uncomfortable.

Disability glare prevents vision. A popular example is holding a glossy magazine at a certain angle; a veiling reflection results, impairing our reading of the page.

Color. The color quality of a lamp is revealed as its color temperature rating and Color Rendering Index (CRI) rating. For a detailed description of these metrics, see Color Metrics

FIXTURE EFFICIENCY

There are two ways to look at a light fixture's (luminaire's) efficiency; one indicates how well the lighting system transforms electrical input into useful light output, and the other indicates how well the fixture itself transmits light from the lamp(s) to the workplane.

Electrical Efficiency. Lighting systems require electrical input to work. This input is measured in watts (W), a measure of required electric power. A lighting system's rated input wattage, therefore, is the amount of power required for it to work at any given instant of time.

Lamp manufacturers publish nominal wattage ratings for their lamps; when fluorescent and HID lamps are operated as a system with a ballast, however, a new rated wattage will result, published by the ballast manufacturer. Ballast manufacturers publish up to three input wattage ratings. The ANSI number is the result of a standardized ANSI test of that given ballast manufacturer's ballast operating a given compatible lamp type (often called the "bench test" because the lamps and ballasts are operated bare on a bench). The next one or two are the manufacturer's ratings for tests in actual open and/or enclosed fixtures.

While the manufacturer's ratings can be considered more realistic (because the testing takes place closer to actual field conditions), the ANSI number should be used when comparing different ballasts because it reflects the results of a common, standardized test procedure.

Therefore, one way to compare the electrical efficiency of lamp-ballast systems is to determine a common light output level, then compare the input wattage for various systems.

A more popular way of achieving a comparison of the relative efficiencies of lighting systems is to use efficacy, expressed in lumens per watt (LPW or lm/W). To determine a system's efficacy, divide its lumen output by its rated input wattage.

When lighting professionals apply the results of efficiency to actual system operation (usually to determine the operating cost savings of a retrofit, they need to determine the amount of energy the lighting system consumes, not just its input wattage. To calculate the energy use of a lighting system, multiply input wattage (W) x time (hours of operation during a year).

Example for Lighting System:



Input Wattage100W
Lumen Output 10,000 lm
Efficacy 100 LPW 10,000 lm ÷ 100W
Hours of Operation3,120 h5 days/week x 12 hours/day x 52 weeks/year
Energy Use312,000 Wh100W x 3,120 hrs/year
Energy Use312kWh312,000 watt-hours (Wh) ÷ 1,000 = 312 kilowatt-hours (kWh)
Utility Charge/kWh$0.075
Energy Cost/Year$23.40312kWh x $0.075/kWh

Color Temperature (K) & Color Rendering (CRI)

What is Color Rendering Index (CRI)?
Color rendering describes how a light source makes the color of an object appear to human eyes and how well subtle variations in color shades are revealed. The Color Rendering Index (CRI) is a scale from 0 to 100 percent indicating how accurate a "given" light source is at rendering color when compared to a "reference" light source.
The higher the CRI, the better the color rendering ability. Light sources with a CRI of 85 to 90 are considered good at color rendering. Light sources with a CRI of 90 or higher are excellent at color rendering and should be used for tasks requiring the most accurate color discrimination.
It is important to note that CRI is independent of color temperature (see discussion of color temperature). Examples: A 2700K ("warm") color temperature incandescent light source has a CRI of 100. One 5000K ("daylight") color temperature fluorescent light source has a CRI of 75 and another with the same color temperature has a CRI of 90.
To further understand the physics of color rendering, we need to look at spectral power distribution.

The visible part of the electromagnetic spectrum is composed of radiation with wavelengths from approximately 400 to 750 nanometers. The blue part of the visible spectrum is the shorter wavelength and the red part is the longer wavelength with all color gradations in between.
Visible Spectrum
Spectral power distribution graphs show the relative power of wavelengths across the visible spectrum for a given light source. These graphs also reveal the ability of a light source to render all, or, selected colors.
Below see how a typical spectral power distribution graph for daylight.
Daylight Spectral Power Distribution
Notice the strong presence (high relative power) of ALL wavelengths (or the "full color spectrum"). Daylight provides the highest level of color rendering across the spectrum.
Compare the daylight spectral power distribution with that for a particular fluorescent lamp.
Daylight Spectral Power Distribution
The most obvious difference is the generally lower level of relative power compared to daylight - - except for a few spikes. All wavelengths (the "full spectrum) are again present but only certain wavelengths (the spikes) are strongly present. These spikes indicate which parts of the color spectrum will be emphasized in the rendering of color for objects illuminated by the light source. This lamp has a 3000K color temperature and a CRI of 82. It produces a light that is perceived as "warmer" than daylight (3000K vs. 5000K). It's ability to render color across the spectrum is not bad, but certainly much worse than daylight. Notice the deep troughs where the curve almost reaches zero relative power at certain wavelengths.
Here is another fluorescent lamp.
Daylight Spectral Power Distribution
This spectral power distribution looks generally similar to the one above except it shows more power at the blue end of the spectrum and less at the red end. Also, there are no low points in the curve that come close to zero power. This lamp has a 5000K color temperature and a CRI of 98. It produces light that is perceived as bluish white (similar to daylight) and it does an excellent job of rendering colors across the spectrum.
Above are links to linear and compact fluorescent light bulbs from Topbulb that have a CRI of 90 or higher. If you want a high color rendering bulb to produce light perceived as warm white, choose a bulb with a color temperature of 3000K or 3500K. If you want a high color rendering bulb to produce light perceived as white, choose a bulb with a color temperature of 4000K. For a bulb that simulates daylight, choose a color temperature of 5000K or higher.
Note: all incandescent and halogen light bulbs, by definition, have a CRI close to 100. They are excellent at rendering color. However, except for some halogen bulbs, most incandescents produce a warm 2800K color temperature. The only way to achieve the bluish white appearance of daylight with incandescent bulbs is to use bulbs coated with neodymium. However, these bulbs have a CRI much lower than 90. They are not good for accurate color rendering across the spectrum.

Window Covering Design

The selection of blinds, window coverings, or the lack thereof is likely the most crucial choice a designer will make when seeking to ensure visual comfort while maintaining daylight performance over time. We have all seen buildings where blinds are down continuously. Typically, this is associated with visual discomfort (glare). The most common source of glare issues in daylighting is a line of sight to the disk of the sun. Selecting a window covering that is opaque enough to block the sun, such as fabric window shades with 3% or less openness or horizontal blinds, can control this phenomena.

Manually operated blind systems can be very effective if properly used. More specifically, a 2" horizontal blind with a white finish can function as a series of mini light shelves casting indirect light into the space when desired. However, they rely on and require constant user attention to maintain complete glare control while achieving maximum daylight performance. For this reason, blinds or shades are often permanently deployed at the ¡°worst case scenario¡± position to maintain visual comfort throughout the day and year. This typically results in poor daylight performance and the elimination of views to the exterior.

Automated glare control has the distinct advantage of being deployed only when needed and retracting without user intervention when direct sunlight is no longer present to allow for unimpeded diffuse daylight. In most cases, this will deliver longer periods of effective daylight contribution, increased electric lighting power savings, and longer durations of unobstructed views to the exterior. Automation of glare control may provide the most persistent daylight performance where low angle direct sun is present during extended periods of occupancy.

< Direct sunlight can cause visual discomfort. Shutting the blinds here would eliminate the benefit of the daylight.




Example of split window covering strategy to preserve views or block sun where needed, allowing for indirect light into space. >

















Shading and Exposure Tips:



  • North - Shading may only be needed in early morning or late afternoon.
  • South - Good access to strong illumination but varies throughout the year. Shading is easier than East/West.
  • East/West - Shading is difficult but critical for comfort.

Locating Lights, Transforwers,Materials And Dccessories Required

Show Typical Switched Wiring Circuits For A Lighting Installation


Whichever type of fitting you intend to use, draw a scale floor plan of the room, clearly mark where items are and where you wish relevant lights to be. When you have completed your plan, mark the ceiling / wall with the centre position of the fitting, making sure you mark the position of cutouts, before cutting or drilling, ensuring there are no obstructions, cable or pipes behind. Fitting lights on the ground floor may require you to have access to the floor above so ensure floorboards can be accessed.

If installing recessed down lights ensure there is enough clearance in the ceiling void, you will find minimum distances stated in the supplied instructions. Ensure the integrity of any fire barrier is maintained especially where there is a dwelling above the site of the fitting(s).



FIG. 6 show typical switched wiring circuits for a lighting installation.


alternatively you can use the existing 230V supply from the loop-in terminals of a ceiling rose supplying existing 230V lighting. Always read the light fittings instructions before attempting any work and if in doubt, consult a qualified electrician. Lighting circuits are usually controlled from a 5amp fuse at the main board and most new installations require this to be protected by an RCD operating at 30mA. In a two-storey house there are usually two lighting circuits, one for each floor.

Using the above information, you should now be able to calculate the amount of cable and where any switches should go. NOTE: always allow extra cable as it is easier to trim back than to add. This will also give you some flexibility if you have to adjust the positioning of a fitting.

Fitting Lights And Electrical Connections


Installing a light fitting is straightforward but at this stage don't fit lamps into their housings. Once all the cabling is in place you can then fix any brackets using suitable fixings ( taking care not to drill or screw through any cables ). Ensure all terminations are secure and comply with the Wiring Regulations that your light fitting complies with BS EN 60598, the British Standard for light fittings.

NOTE: Fittings classed as Double Insulated ( Class II ) or SELV ( Class III ) do not require an earth and fitting instructions should be followed. TIP: When using multiple lamp fittings, or when low voltage fittings are supplied via a transformer, a bulb / lamp reaches the end of its life; it is good practice, to replace as soon as possible. Failure to do so may cause 'overvolting' of the other bulbs / lamps and could reduce their lifespan by up to 50%. Always ensure that the bulbs / lamps are sufficiently cool before replacing.

Detection Of Motion


with the European Standard for luminaries (BS EN 60598) and carry a CE mark. Depending on where the light fitting is to be sited will determine the degree of protection the product will need against ingress of moisture. This is known as an IP rating i.e. IP44. Simply put, the first number of an IP rating (0-6) is the degree of protection against debris, dust and even 'little fingers' getting in. The second number (0-8) is its resistance to moisture. IP68 is the highest degree of protection offered against dust, solid objects & moisture.

Outdoor Light Of Materials And Dccessories Required


Outdoor light fittings will require some maintenance, so choose one made from a material suitable for the local environmental conditions i.e. if you live near to the sea, select a plastic or marine grade stainless steel product that will require minimal cleaning and is not prone to corrosion. Always check manufacturer's zcare instructions.

Having decided, what, where, how you wish to light and how many different moods you want to create, make a plan of your garden, identifying lengths, quantities of materials and accessories required. These may include switches, P.I.R. sensors, conduit, armoured cable (above 50V), an RCD, fixings, weatherproof junctions boxes, cable joints, glands etc.

NOTE: Outdoor Fittings operating under 50V can use conduit to protect the cable. Fittings operating above 50V must use armoured cable and be protected by a RCD, with a residual operating current not exceeding 30mA.

Once you have selected your fittings and accessories, using your plan, physically mark out the areas in your garden where the lighting is to be sited and the cable is to be run. Prepare the ground for the cables by digging channels - for cables operating at above 50V or where the ground is likely to be disturbed, the trench must be at least 500mm deep.

The cable route should be marked with yellow and black tape. It should be just 150mm below the surface, above buried cable; this is to warn persons excavating the ground in the future that a cable is present. It is also a good idea to keep a garden plan showing all cable routes and depths for future reference.

NOTE: When laying cable, always leave an extra length for any last minute adjustments; it is easier to reduce the length than it is to add. Don't back fill until you have completed, tested and are happy with the positioning of the system.

When installing recessed ground lighting in a drive or pathway, you should provide suitable drainage; bedding the base of the fitting onto gravel can easily do this.

Once all the cabling is in place and you are happy with the location of the fittings, make sure the securing method is suitable for the size and weight of the fitting, the surface to which it is to be fixed and its exposure to the elements. When all this is done, connect the supply cable, re-check all connections and fit bulbs / lights. Only when you are happy with the installation and it has been checked, can an 'Authorised Competent Person' connect the mains power supply. Switch on and test. Back fill any trenches and make good.

Even the best garden lighting designers don't always get it right first time. If this happens to you, it may just be a case of a little adjustment or even some trial and error but it's worth persevering. You can easily add a new circuit or more lights if necessary.

NOTE: Always keep your garden lighting plans for future reference.

All outdoor electrical work must conform to BS 7671 the current IEE wiring regulations, and Part P of Building Regulations, you are advised to check with your local authorities Building Control Department, or an Authorised Competent Person, before starting. If in any doubt about electrical work, contact a qualified person.

COB LED Light Tube T10

  • COB LED Light Tube T10 9W 14W 19W 24W
  • Up to 80% energy savings.
  • Fits conventional fluorescent light fixture.
  • Super high efficiency lumen output.
  • High-efficient power design (Constant current).
  • Simple repair and maintenance with (Chip on board ) LEDs modular design.
  • Absolutely no flicker for eye protection
  • UV or IR free for skin & eye benefit.
  • Lower burden on air-conditioner.
  • Instant lighting-on with no flickering.
  • Excellent durability and stanbility at high temperature.

LED Light Tube T10 Using A Surface Light Emitting ( Chip On Board ) COB LEDs


COB LED Light Tube T10 9w / 14w / 19w / 24w

ItemCOB LED Tube T10 9wCOB LED Tube T10 14wCOB LED Tube T10 19wCOB LED Tube T10 24w
Style No#AL-T10-9WAL-T10-14WAL-T10-19WAL-T10-24W
Lamp holder / BaseG 13
Wattage9 w14 w19 w24 w
Luminous fluxCool white :
650 - 750 Lm
Cool white :
950 - 1050 Lm
Cool white :
1300 - 1400 Lm
Cool white :
1600 - 1700 Lm
Warm white :
550 - 650 Lm
Warm white :
850 - 950 Lm
Warm white :
1200 - 1300 Lm
Warm white :
1500 - 1600 Lm
Qtp of LED135210285360
Color temperatureCool white : 6000 K ± 300 K
Warm White : 3000 K ± 300 K
Color rendering index Ra≥ 75 Ra
Casing materialPC + Airlines Die - Cast aluminum
Power Factor ≥ 90%
Light colorWarm white / Cool white
Nominal voltage(product)Ac85 - 265V
Operating frequency50 - 60 Hz
Dimensions:
L ×
Diameter : Φ
L: 588 mm
Φ : 30 mm
L: 894 mm
Φ : 30 mm
L: 1198 mm
Φ : 30 mm
L: 1498 mm
Φ : 30 mm
led tube light t5
Lifespan30,000 - 50,000 H
Packging unit25pc
Dimensions in
H × W × L
L : 220 mm × 210 mm × 650 mmL : 220 mm × 210 mm × 950 mmL : 220 mm × 210 mm × 1250 mmL : 220 mm × 210 mm × 1520 mm
Gross weight8 kg10.25 kg14.15 kg17.55 kg
Volume :
L X W X H
30.030 Cubic dec43.890 Cubic dec57.750 Cubic dec70.224 Cubic dec
 

Application:
Suitable for the offices, schools, basement parkings, restaurants, hotels, hypermarkets and many other places because the COB LED Tube Lamps do not contain poisonous and help with cost-saving and carbon reduction programmes. Available in various lengths and color temperatures, the Welland LED tube lamps come in various lengths and are designed to replace conventional fluorescent tube lamps. The tube lamps are manufactured with reliable plastic tube and high quality (Chip on board ) LEDs module, so are extremely safe and durable.

Attention:
- Please cut off the main power supply before installation.
- The starter, ballast, electrical switch are not required for LED tube.
- To remove the electric switch and reconstruct the circuit by professional electrician is suggested.
- This COB LED tube is not Dimmable - Do not connect with the Dimmer.
- Do not use for Emergency Fittings.

COB Dimmable LED Downlight Rotatable LED Ceiling Lamp

  • Light Source: LED surface light source,COB (Chip-on-Board) design
  • Body Material: Aluminum.
  • Radiator Temp:< 55 degree.
  • Radiator Caft : 6063 aluminum cold forging.
  • Environment-friendly and no UV or IR radiation.
  • No dazzling and mild color with light bending effect.
  • Long lifespan, low cost of maintenance.
  • Transformer is at the COB LED Downlight directly attached, including a terminal block for power line .
  • Easy to install and maintain, and normal base type E can be matched.
  • Easy to install and maintain, replacement of traditional bulbs and no subsidiary fixture.
  • Available for Switch controll (dimmable) or Non dimmable types.
  • Swivel range : 30 °

COB LED Downlight Speciality : Compatible with most SCR dimmer,integration of controlling several light available,no flicker.


COB Dimmable LED Downlight Rotatable LED Ceiling Lamp ( option of dimmable or not-dimmable )

Nominal voltage(product)Ac85 - 265V
Operating frequency50 - 60 Hz
Lifespan30,000 H
Radiator temp :< 55°C
Power factor :> 0.9
Casing materialRadiator temp : 6063 aluminum cold forging
Body material:aluminum
Style No#AL-OCL203AL-OCL205AL-OCL303AL-OCL305
Wattage2 Light × 3w2 Light × 5w3 Light × 3w3 Light × 5w
Luminous fluxWarm white :
> 360 Lm

Cool white :
> 420 Lm

Nature white :
> 480 Lm
Warm white :
> 600 Lm

Cool white :
> 700 Lm

Nature white :
> 800 Lm
Warm white :
> 540 Lm

Cool white :
> 630 Lm

Nature white :
> 720 Lm
Warm white :
> 900 Lm

Cool white :
> 1050 Lm

Nature white :
> 1200 Lm
Luminous efficacyWarm white : 60 Lm/w
Cool white : 70 Lm/w
Nature white : 80 Lm/w
Color temperatureWarm white : 3000 K
Cool white : 4000 K
Nature white : 6400 K
Color rendering index RaWarm white : > 80 Ra
Cool white : > 75 Ra
Nature white : > 75 Ra
Light colorWarm white
Cool white
Nature white
Packging unitContains 10 Piece
Dimensions in
H × W × L
210 mm × 280 mm × 580 mm
Gross weight9.2 Kg
Volume34.104 Cubic dec

This discreet Downligh ter with minimal design is the ideal solution for the lighting requirements of hotels, retail and fitness areas and spaces that require exact light from compact fittings that are easy to install and maintain.
Available in two versions - fixed and adjustable - Pinhole can be installed in false ceilings with thickness from 1 to 20 mm with stainless steel springs. The front ring contains an accessory-holding ring.

Dimmable LED Downlights are used widely for general ambient lighting in:

Home /office lighting,display case lighting
Under cabinet lighting
Art lighting

Dimmable COB LED Downlight Round Swivel

  • Light Source: LED surface light source,COB (Chip-on-Board) design
  • Body Material: Aluminum.
  • Radiator Temp:< 55 degree.
  • Radiator Caft : 6063 aluminum cold forging.
  • Environment-friendly and no UV or IR radiation.
  • No dazzling and mild color with light bending effect.
  • Long lifespan, low cost of maintenance.
  • Transformer is at the COB LED Downlight directly attached, including a terminal block for power line .
  • Easy to install and maintain, and normal base type E can be matched.
  • Easy to install and maintain, replacement of traditional bulbs and no subsidiary fixture.
  • Available for Switch controll (dimmable) or Non dimmable types.
  • Swivel range : 30 °

COB LED Downligh Speciality : Compatible with most SCR dimmer,integration of controlling several light available,no flicker .


COB Dimmable LED Downlight Round Swivel ( option of dimmable or not-dimmable )

Nominal voltage(product)Ac85 - 265V
Operating frequency50 - 60 Hz
Lifespan30,000 H
Radiator temp :< 55°C
Power factor :> 0.9
Casing materialRadiator temp : 6063 aluminum cold forging
Body material:aluminum
Style No#AL-CCL03AL-CCL05
Wattage3w5w
Luminous fluxWarm white :
> 180 Lm

Cool white :
> 210 Lm

Nature white :
> 240 Lm
Warm white :
> 300 Lm

Cool white :
> 350 Lm

Nature white :
> 400 Lm
Luminous efficacyWarm white : 60 Lm/w
Cool white : 70 Lm/w
Nature white : 80 Lm/w
Color temperatureWarm white : 3000 K
Cool white : 4000 K
Nature white : 6400 K
Color rendering index RaWarm white : > 80 Ra
Cool white : > 75 Ra
Nature white : > 75 Ra
Light colorWarm white
Cool white
Nature white
Dimensions :Depth :66.5 mm

Outer diameter : Φ: 85 mm

Diameter : Φ: 75 mm
COB LED Downlight Round Swivel

Dimensions images
Packging unitContains 50 Piece
Dimensions in
H × W × L
210 mm × 480 mm × 480 mm
Gross weight14.5 Kg
Volume48.384 Cubic dec

This discreet Downligh ter with minimal design is the ideal solution for the lighting requirements of hotels, retail and fitness areas and spaces that require exact light from compact fittings that are easy to install and maintain.
Available in two versions - fixed and adjustable - Pinhole can be installed in false ceilings with thickness from 1 to 20 mm with stainless steel springs. The front ring contains an accessory-holding ring.

Dimmable LED downlights are used widely for general ambient lighting in:

Home /office lighting,display case lighting
Under cabinet lighting
Art lighting

COB Dimmable LED Downlight

  • Light Source: LED surface light source,COB (Chip-on-Board) design
  • Body Material: Aluminum.
  • Radiator Temp:< 55 degree.
  • Radiator Caft : 6063 aluminum cold forging.
  • Environment-friendly and no UV or IR radiation.
  • No dazzling and mild color with light bending effect.
  • Long lifespan, low cost of maintenance.
  • Transformer is at the COB LED Downlight directly attached, including a terminal block for power line .
  • Easy to install and maintain, and normal base type E can be matched.
  • Easy to install and maintain, replacement of traditional bulbs and no subsidiary fixture.
  • Available for Switch controll (dimmable) or Non dimmable types.
  • Swivel range : 30 °

COB LED Downlight Speciality : Compatible with most SCR dimmer,integration of controlling several light available,no flicker


COB Dimmable LED Downlight ( option of dimmable or not-dimmable )

Nominal voltage(product)Ac85 - 265V
Operating frequency50 - 60 Hz
Lifespan30,000 H
Radiator temp :< 55°C
Power factor :> 0.9
Casing materialRadiator temp : 6063 aluminum cold forging
Body material:aluminum
Style No#AL-CD03AL-CD05AL-CD07AL-CD10AL-CD15
Wattage3w5w7w10w15w
Luminous fluxWarm white :
> 180 Lm

Cool white :
> 210 Lm

Nature white :
> 240 Lm
Warm white :
> 300 Lm

Cool white :
> 350 Lm

Nature white :
> 400 Lm
Warm white :
> 420 Lm

Cool white :
> 490 Lm

Nature white :
> 560 Lm
Warm white :
> 600 Lm

Cool white :
> 700 Lm

Nature white :
> 800 Lm
Warm white :
> 900 Lm

Cool white :
> 1050 Lm

Nature white :
> 1200 Lm
Luminous efficacyWarm white : 60 Lm/w
Cool white : 70 Lm/w
Nature white : 80 Lm/w
Color temperatureWarm white : 3000 K
Cool white : 4000 K
Nature white : 6400 K
Color rendering index RaWarm white : > 80 Ra
Cool white : > 75 Ra
Nature white : > 75 Ra
Light colorWarm white
Cool white
Nature white
Dimensions :Depth :90 mm

Outer diameter : Φ: 101.5 mm

Diameter : Φ: 75 mm
Depth :102.5 mm

Outer diameter : Φ: 112 mm

diameter : Φ: 85 mm
Depth :102.5 mm

Outer diameter : Φ: 112 mm

diameter : Φ: 85 mm
Depth :110 mm

Outer diameter : Φ: 143 mm

diameter : Φ: 105 mm
Depth :110 mm

Outer diameter : Φ: 143 mm

diameter : Φ: 105 mm
Dimensions images ( 3w 5w )

Dimensions images ( 5w 7w )

Dimensions images ( 10w 15w )

Packging unitContains 16 Piece
Dimensions in
H × W × L
280 mm × 320 mm × 620 mm
Gross weight6.72 Kg
Volume55.552 Cubic dec

This discreet Downligh ter with minimal design is the ideal solution for the lighting requirements of hotels, retail and fitness areas and spaces that require exact light from compact fittings that are easy to install and maintain.
Available in two versions - fixed and adjustable - Pinhole can be installed in false ceilings with thickness from 1 to 20 mm with stainless steel springs. The front ring contains an accessory-holding ring.

Dimmable LED downlights are used widely for general ambient lighting in:

Home /office lighting,display case lighting
Under cabinet lighting
Art lighting

LED DownLight Manufacturers COB Technology - Features & benefits

  • Environment Friendly : LED backlighting eliminates the traces of mercury found in cold-cathode fluorescent lamps, thus meeting mandates for the reduction of hazardous substances. RoHS compliant product, No Cadmium, Lead, or Mercury. Unlike fluorescent, there are no concerns over disposal.
  • High Energy Efficient: Only 20% power consumption of halogen lamp and incandescent lamp.
  • Low Heat Generation : Excellent heat dissipation design,surface temperature is lower 58°C, Junction temperature lower than 102°C.
  • Natural Light : Superior colour rendering over other LED sources due to unique PLF technology; High pupil lumen factor.
  • Ergonomic Light : No EMI, ballast noise, UV or glare. Non-flickering light reduces eye strain, headaches and other workplace complaints associated with fluorescent lighting. Remote controlled dimming and (on E models only) colour temperature adjustment to suit changing activities and moods.
  • High Uniformity : The backlight unit demonstrates a brightness uniformity of more than 85 percent and a color uniformity (Δu'v') of less than 0.007 in CIE1976 LUV color space. The results are equivalent to the performance of a compact fluorescent light source.

LED Downlight Using A Surface Light Emitting ( Chip On Board ) COB LEDs

Dimmable COB LED Downlight

  • Wattage : 3W / 5W / 7W / 10W / 15W
  • Color temperature : 3000K / 4000K / 6400K
  • Luminous flux(3W) : 180LM / 210LM / 240LM
  • Luminous flux(5W) : 300LM / 350LM / 400LM
  • Luminous flux(7W) : 420LM / 490LM / 560LM
  • Luminous flux(10W) : 600LM / 700LM / 800LM
  • Luminous flux(15W) : 900LM / 1050LM / 1200LM
  • Round COB LED Downlight : Available for switch controll (dimmable) or Non dimmable types.

COB LED Downlight Round Swivel

  • Swivel range: 30 °
  • Wattage : 3W / 5W
  • Color temperature : 3000K / 4000K / 6400K
  • Luminous flux(3W) : 180LM / 210LM / 240LM
  • Luminous flux(5W) : 300LM / 350LM / 400LM
  • Round Swivel COB LED Downlight : Available for switch controll (dimmable) or Non dimmable types.

COB LED Downlight Rotatable LED Ceiling Lamp

  • Swivel range: 30 °
  • Wattage : 3 × 3W / 3 × 5W
  • Color temperature : 3000K / 4000K / 6400K
  • Luminous flux(3W) : 540LM / 630LM / 720LM
  • Luminous flux(5W) : 900LM / 1050LM / 1200LM
  • Dimmable COB LED Downlight Rotatable LED Ceiling Lamp : Available for switch controll (dimmable) or Non dimmable types.